Most ground rods will look similar to the rod sticking up out of the soil.
WRONG RIGHT
Almost all homes and many commercial and industrial facilities in the United States have electrodes installed improperly. For some unknown reason the Authority Having Jurisdiction (AHJ), defined in the NEC is ignoring these NEC articles. They are approving the wrong installation method and not requiring the right method. In addition, unless the state or local AHJ automatically requires two (2) ground rods; they are not requiring the contractor to verify the twenty-five (25Ω) Ohms or less requirement. If it does not meet that requirement then another ground rod must be installed.
Below are the current 2023 National Electrical Code (NEC) articles describing installation requirements for Rods, Pipes, and Plate Electrodes.
Once you read the NEC articles you will understand the proper methods of installing these electrodes.
Here are the major requirements in those NEC articles:
250.53 Grounding Electrode System Installation.
250.53(A) Rod, Pipe, and Plate Electrodes.
250.53(A)(1) Below Permanent Moisture Level.
250.53(A)(2) Supplemental Electrode Required.
250.53(A)(3) Supplemental Electrode.
250.53(A)(4) Rod and Pipe Electrodes.
250.10 Protection of Ground Clamps and Fittings.
250.53(A)(5) Plate Electrode.
250.53(B) Electrode Spacing.
Comments